Fire sprinkler systems are one of the most critical safeguards in commercial buildings, but they require diligent year-round maintenance to remain effective. A well-maintained sprinkler system dramatically increases the likelihood of controlling a fire early, protecting lives and property. In fact, NFPA data shows that when sprinklers fail, a leading cause is lack of maintenance or closed valves. Routine inspections and tests throughout the year ensure that every component – from sprinkler heads to fire pumps – will operate correctly in an emergency. For building owners and safety managers, maintaining compliance with fire codes is not only a legal obligation but also a wise business decision that can reduce liability and insurance costs. In Ohio, these practices are especially important as the state’s fire code mandates adherence to national standards for sprinkler upkeep. By investing in regular maintenance all year, you safeguard your facility and gain peace of mind that your sprinkler system will perform when it’s needed most.
Several NFPA codes govern fire sprinkler systems, setting standards for installation and maintenance. The primary reference is NFPA 25 – Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems. NFPA 25 provides the minimum requirements for how often and in what manner sprinklers, valves, fire pumps, and related components must be inspected and tested to ensure they remain in working order. In Ohio, the Ohio Fire Code has adopted NFPA 25 by reference, meaning compliance with NFPA 25’s provisions is effectively required by law for commercial buildings.
Other relevant NFPA codes include NFPA 13 – Standard for the Installation of Sprinkler Systems (governing proper design and installation) and NFPA 20 – Standard for the Installation of Stationary Fire Pumps, which ensure systems are built to perform optimally. However, once your sprinkler system is installed and operational, NFPA 25 is the key standard that outlines the ongoing inspection, testing, and maintenance (ITM) tasks needed to keep the system compliant and ready. Adhering to NFPA 25 helps maximize system integrity and reliability, and it is used by fire marshals and insurance inspectors as the benchmark for sprinkler maintenance.
It's important to note that building owners are ultimately responsible for maintaining their fire protection systems in compliance with NFPA 25. Chapter 4 of NFPA 25 explicitly assigns the responsibility of all ITM activities to the property owner (or their designated representative). This means owners must ensure all required inspections and tests are conducted on schedule and that any problems are corrected promptly. Failing to do so can lead to non-compliance citations, increased fire risk, or voided insurance coverage. Fortunately, owners can delegate these duties to qualified professionals – which is where a trusted fire protection service partner comes in (more on that later). The key is that regular, code-compliant maintenance is not optional; it is a year-round commitment embedded in the fire codes and NFPA standards that Ohio abides by.
Fire sprinkler maintenance isn’t a once-a-year task – it’s an ongoing process with weekly, monthly, quarterly, annual, and multi-year activities as defined by NFPA 25. These routine checks and tests are designed to catch potential issues early and verify that all components will function during a fire emergency. Below is an overview of what needs to be done on a routine basis for a typical commercial sprinkler system:
Sprinkler system risers with multiple control valves and gauges. Regular inspection of such equipment ensures valves remain open and free of tampering, gauges register normal pressures, and emergency signs or tags are intact. NFPA 25 mandates periodic visual inspections of sprinkler components to catch issues like closed valves or leaks before a fire occurs. Building staff should verify that nothing blocks or interferes with sprinkler heads (no paint, dust, or stock piled too high) as part of routine housekeeping, since obstructed or painted heads can delay or prevent proper activation during a fire.
A common question building owners have is which maintenance tasks can their own facility team handle versus which require a licensed fire protection technician. NFPA 25 defines that all inspections, testing, and maintenance must be performed by qualified individuals – meaning someone who is trained, competent, and meets any certification requirements of the Authority Having Jurisdiction. In Ohio, this typically means that the more complex tests and any repair or alteration work must be done by state-certified fire protection contractors. Ohio’s regulations require companies and technicians to be certified to service, test, or repair fire sprinkler systems for hire. However, there are basic inspection activities that knowledgeable building personnel can carry out as part of their regular maintenance rounds. Let’s clarify the division of responsibilities:
In summary, unlicensed (in-house) personnel can handle routine inspections and simple upkeep, while licensed technicians handle the formal testing, repairs, and any task that requires technical manipulation of the system. This collaborative approach ensures cost-effective maintenance – your staff can catch obvious issues early, and your fire safety contractor can perform the detailed work to keep the system in peak condition and code compliance. Always err on the side of safety: if there’s ever a doubt or an issue found, involve a professional. It’s better to be proactive and have a certified sprinkler technician correct a problem than to risk improper fixes that could lead to system failure.
If your building has a fire pump as part of the sprinkler system, maintaining this pump is as important as the sprinklers themselves. Fire pumps (governed by NFPA 20 for installation and NFPA 25 for maintenance) provide the necessary water pressure to sprinklers in taller or larger buildings, or in facilities where the water supply is not sufficient on its own. A fire pump that fails to start or perform can severely compromise your sprinkler system’s effectiveness in a fire, so regular pump inspections and testing are critical. NFPA 25 outlines specific fire pump test schedules depending on the type of pump:
Fire pump assembly in a commercial building, including the electric motor, controller, and piping. NFPA 25 requires regular testing of such pumps to ensure they will run and deliver adequate pressure when needed. For instance, diesel-driven fire pumps must undergo a no-flow “churn” test weekly, and most electric fire pumps must be tested monthly under no-flow conditions. During a churn test, the pump is run without discharging water, verifying that it starts automatically and runs without overheating. In addition, an annual full-flow performance test is conducted to measure the pump’s output at various flow rates (100% and 150% of rated capacity) to ensure it meets design pressure. These annual flow tests are rigorous and require qualified personnel in attendance to carry them out safely.
For electric fire pumps, NFPA 25 allows a monthly churn test in many cases, except where the pump is critical (for example, in very high-rise buildings or where the fire department connection can’t support the system). In those special cases, even electric pumps might need weekly testing. Diesel fire pumps, on the other hand, require weekly exercise without exception – not only to test the pump, but also to keep the diesel engine in good running condition (including checking oil pressure, engine temperature, battery charge, and fuel supply during the test). Every fire pump should also get a thorough annual maintenance service: changing engine oil and filters (for diesels), cleaning strainers, confirming the automatic start features, and calibrating pressure sensors in the controller. Pump rooms should be inspected frequently to ensure they are free of clutter, properly ventilated, and heated (at least 40°F to prevent the pump or pipes from freezing). Ohio’s climate makes pump room heating and generator block heaters (for diesel engines) very important in winter.
Beyond the pump, a complete fire sprinkler system has other components that need care. Back flow preventers, which are usually located near the sprinkler riser, must be tested annually to confirm they will allow full water flow to the system while preventing reverse flow. Typically, a back flow test is done concurrently with sprinkler service by a licensed tester. Standpipe systems (if present in high-rises or large facilities) require their own inspections – for example, hose connections should be inspected quarterly and a full flow test from the roof outlets every 5 years to ensure adequate pressure. Fire department connections (FDC) should be checked to make sure caps are in place and clapper valves function, so the fire department can boost your system if needed. All valves (including sectional control valves, alarm valves, and pressure-reducing valves) need periodic exercise to prevent seizure. If your system uses antifreeze loops (to protect small sections of pipe from freezing), NFPA 25 requires yearly testing of the antifreeze solution before the winter season to ensure it’s still at the proper concentration. Neglecting any one component can create a weak link in the chain; for instance, a closed sectional valve or a clogged back flow preventer can render your sprinklers useless despite all other sprinklers being in perfect shape. That’s why a holistic maintenance approach is important – a professional technician will check all aspects of the system (sprinklers, piping, valves, pump, back flow, etc.) during scheduled service visits to ensure nothing is overlooked.
Maintaining a commercial fire sprinkler system in Ohio may seem daunting with all these requirements, but this is where Holmes Fire & Safety becomes your valued partner. We pride ourselves on being a one-stop solution for all your fire sprinkler needs, handling everything from routine weekly check-ins to the annual inspections, testing, and any repairs – so you don’t have to worry. Our team of licensed fire protection technicians is fully versed in NFPA 25 and Ohio fire code requirements, ensuring that your building stays in full compliance year-round. We take care of scheduling all required inspections and tests (weekly, monthly, quarterly, annual, and beyond) and keep meticulous records, so you can readily demonstrate your compliance to fire marshals or insurance auditors.
With Holmes Fire & Safety, you can trust that every sprinkler head, valve, and fire pump in your system is maintained to the highest standard. We perform the necessary tests with minimal disruption to your operations, and we promptly address any deficiencies with qualified maintenance and repairs. Our comprehensive service means we assume full responsibility for your fire sprinkler system’s readiness – giving building owners and safety managers complete peace of mind. Instead of juggling multiple vendors or worrying about missing an inspection deadline, you have a single expert source ensuring nothing is overlooked and your system remains in peak working condition.
Professional, Dependable, Peace of Mind: That’s the Holmes Fire & Safety promise. We understand the stakes – your business, employees, customers, and property all rely on the sprinkler system to work without fail in an emergency. By partnering with us for year-round sprinkler maintenance, you are making a proactive investment in safety and compliance. Let Holmes Fire & Safety handle the complex code requirements and technical work, while you focus on running your business. We’ll ensure your commercial fire sprinkler system is always code-compliant, fully functional, and ready to protect – every day of the year.
Whether you manage an office high-rise, a manufacturing plant, a school, or any commercial facility in Ohio, our team is ready to tailor a maintenance program that fits your needs. Contact Holmes Fire & Safety today to learn how we can keep your fire sprinkler system in top shape year-round, providing reliable protection and unmatched peace of mind for you and your organization.